PRODUCT PARAMETERS
| Frame (AF) | 50 | ||
| Breaking capacity (kA), Icu 415VAC | 5 | ||
| Pole (P) | 2,3 | ||
| Type | ABE52b | ||
| ABE53b | |||
| Rated current (A) | 15,20,30,40,50 | ||
| Technical parameter IEC/EN60947-2 | |||
| Rated voltage (V), Ue (50/60Hz) | 600 | ||
| Rated voltage (V), Ue (DC) | 250 | ||
| Rated insulation voltage (V), Ui (50/60Hz) | 690 | ||
| Rated pulse voltage (kV), Uimp | 6 | ||
| Extreme short-circuit breaking capacity[Icu](kA) | AC 50/60Hz | 220V/240V | 10 |
| 380V | 7.5 | ||
| 415V | 5 | ||
| 440/460V | 5 | ||
| 480/500V | 2.5 | ||
| 600V | 2.5 | ||
| DC | 125V | 5 | |
| 250V | 2.5 | ||
| Service breaking capacity[Ics=%Icu] | 50 | ||
| Endurance(Durability) | Mechanical | 8500 | |
| Electrical | 1500 | ||
| Accessory | |||
| Internal | Auxiliary AUX | √ | |
| Alarm switch ALT | √ | ||
| Shunt trip SHT | √ | ||
| Under voltage trip UVT | √ | ||
| External | Rotary Handle | √ | |
| Insulation terminal cover | √ | ||
| Insulation barrier | √ | ||
| Wiring behind the board | √ | ||
| Installation and Dimensions | |||
| Dimensions(mm)W*H*D | 75*130*60 | ||
| Weight(kg) | 2/3P | 0.45/0.65 | |